Manufacturer’s Suggested
Annual Maintenance Protocol
For
The Interstitial Float Switch Assembly
The EFG-8000 series of liquid level gauges operates as a very simple gauging device with level
alarm options, and an interstitial alarm option that requires almost no maintenance. This document is
specifically about the interstitial float assembly operation and testing procedures.
The interstitial float device operates as a normally closed circuit device. An interstitial alarm
will visually alternate in the LCD display by showing the letters "ISLA" and the gallons in the tank.
This visual indicator will continue until the open circuit condition is cleared (the float returns to the
bottom position). The Solar Gauge typically operates in a low power mode until it has sensed a greater
than 2% tank volume change. When the gauge detects no liquid level change in the tank it goes into a
power saving mode reducing the refresh timing of the display and alarm soundings. This is important
to understand during testing of the interstitial float assembly and listening for the enunciation.
Although the display will show the alarm in seconds, the enunciator may take up to approximately 90
seconds to enunciate the audible alarm - three short beeps. Once the alarm has sounded it will continue
to enunciate approximately every 90 seconds until cleared.
Operational inspections must be done at least once a year depending on local inspector authority
requirements. The preferred method of testing the assembly is removal from the interstitial cavity.
(Note: pipe fittings must be provided above the interstitial cavity that allow for the inspection and
removal of the interstitial assembly without disconnecting the communication wires.) Hold the
assembly in your hand and inspect for liquid contamination past or present and document the findings.
The preferred method of activation is by turning the assembly upside down. The float must fall freely
and move to both extremes when carefully shaken up and down. If the float does not move freely the
assembly needs replaced. Next, holding the assembly upside down (wires coming out of assembly will
be facing down), watch for the alarm message in the LCD display. You must hold this position until the
three short beeps are heard. Another option is to temporarily place the assembly into a container of
clean water, unleaded gas, or Av-Gas at least two inches deep (with the wires in an upright position).
Test for the alarm under the timing conditions outlined above. Diesel is not a recommended liquid to
test in because it might show false contamination over years of testing. With either method of
testing, the float assembly should cause an interstitial alarm, which confirms correct operation of this
device. When testing has correctly caused an alarm, carefully return the interstitial alarm assembly
down into the bottom of the cavity and make sure all the pipe fittings are sealed against moisture.
If you have questions on your results please contact customer assistance*.